Troubleshooting the powerflex safety option module, Introduction, Status indicators – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual
Page 151: Chapter 12, Introduction status indicators, Troubleshooting the powerflex, Safety option module, Chapter

Rockwell Automation Publication 750-RM001F-EN-P - February 2012
151
Chapter
12
Troubleshooting the PowerFlex Safety Option
Module
Introduction
This chapter provides troubleshooting tables for diagnosing fault conditions
associated with the PowerFlex safety option module.
Status Indicators
The safety option features two indicators to provide status information.
Topic
Page
Indicator
Status
Description
P/F
Green/On
The safety option is operating normally and is in Run mode.
Red/Flashing
A recoverable fault has occurred.
Red/On
A nonrecoverable fault has occurred.
(All other indicators are OFF.)
Red/Green Flashing
The configuration is being downloaded or a firmware
upgrade is in progress.
MP
Green/On
Motion Power is enabled.
Off
Motion Power is disabled.
Red/Flashing
A Motion Power fault has been detected.