Safe Maximum Speed and Direction Monitoring
Chapter 9
Figure 44 - Positive Safe Direction Monitoring Timing Diagram
P42 [Direction Mon] = 1 “Pos Always”
Figure 45 - Negative Safe Direction Monitoring Timing Diagram
P42 [Direction Mon] = 2 “Neg Always”
If motion is detected in the incorrect direction while Safe Direction Monitoring
is active, a Direction fault occurs. If a Direction fault is detected while the safety
option is monitoring motion, the configured P45 [Safe Stop Type] is initiated
and direction monitoring is not performed during the safe stop. If a Direction
fault is first detected after the initiation of the safe stop, then all outputs go to
their faulted state.
For more information about faults, see
.
0
300
Speed
Safe Direction Fault
Time
Safe Direction
0
-300
Speed
Time
Safe Direction
Safe Direction Fault