Editing the configuration – Rockwell Automation 21G PowerFlex 750-Series AC Drives Reference Manual User Manual
Page 130

130
Rockwell Automation Publication 750-RM001F-EN-P - February 2012
Chapter 10
Safety Configuration and Verification
Editing the Configuration
Only authorized, specially-trained personnel can make edits to the configuration.
These personnel should use all supervisory methods available, for example, using
the software password protections.
When authorized, specially-trained personnel make edits, they assume the central
safety responsibility while the changes are in progress. These personnel must also
maintain safe application operation.
You must sufficiently document all edits, including:
• authorization.
• impact analysis.
• execution.
• test information.
• revision information.
This flowchart shows the steps necessary to edit the safety option’s configuration.
Edit the Configuration
Unlock the Configuration
Make Desired Modifications to Safety
Parameters
Apply Changes
Configuration Signature ID Generated
Project Verification Test
Make Required Modifications
Tests
Passed?
Confirm the Project
Record the Configuration Signature ID
Lock the Configuration
Verify the Lock Status and Signature ID
END
Yes
No