Configuring ge egd production exchanges – SATEC PM174 Manual User Manual
Page 64

Chapter 4 PAS Application
Configuring Communications in your
64
Series PM174 Powermeters
The following table lists available network options.
Parameter Options
Default
Device IP Address
192.168.0.203
Network Subnet Mask
255.255.255.0
Network Default Gateway
192.168.0.1
TCP Service Port
502 = Modbus/TCP
20000 = DNP3/TCP
502
Ì
The TCP service port can also be changed trough the COM1
serial port setup: changing the protocol for the port automatically
changes the TCP port for the Ethernet.
To change the Ethernet settings in your meter, select desired
parameters, and then click Send.
NOTES
1. The meter provides the permanent Modbus TCP server
on port 502. Selecting the DNP3 TCP service port
launches the DNP3 TCP server in addition to the Modbus
server allowing simultaneous connections on both ports.
Selecting the Modbus TCP port disables the DNP3 TCP
server.
2. When you change the device network settings through the
Ethernet port, the device port restarts so communication
will be temporarily lost. You may need to wait some
additional time until PAS restores a connection with your
device.
Configuring GE EGD Production
Exchanges
The PM174 provides a GE EGD (Ethernet Global Data) data
producer that supports four data exchanges. Each data