Appendix e data scales – SATEC PM174 Manual User Manual
Page 148

Appendix E Data Scales
148
Series PM174 Powermeters
Appendix E Data Scales
The maximum values for volts, amps and power in the PM174
setup and in communications are limited by the voltage and
current scale settings. See
in Chapter 4 on
how to change the voltage scale in your meter.
The following table defines the meter data scales.
Scale Conditions
Range
Maximum voltage
(V max)
All configurations
Voltage scale
× PT Ratio, V
1
Maximum current
(I max)
All configurations
Current scale
× CT Ratio, A
2, 3
Wiring 4LN3, 3LN3, 3BLN3
V max
× I max × 3, W
Maximum Power
(P max)
4
Wiring 4LL3, 3LL3, 3BLL3,
3OP2, 3OP3, 3DIR2
V max
× I max × 2, W
Maximum
frequency
50 or 60 Hz
100 Hz
1
The default voltage scale is 144V. The recommended
voltage scale is 120V+20% = 144V for using with external
PT’s, and 690V+20% = 828V for a direct connection to
power line.
2
CT Ratio = CT primary current/CT secondary current
3
The default current scale is 2
× CT secondary (2.0A with 1A
secondaries and 10.0A with 5A secondaries)
.
4
Maximum power is rounded to whole kilowatts. With PT=1.0,
it is limited to 9,999,000 W.