beautypg.com

Appendix, Code table – Lenze LDECBBF1xxxxxxHx User Manual

Page 89

background image

Appendix

Code table

10

l

89

LDEDS−CCU210B EN 4.0

Description

Possible settings

Code

Selection

Lenze

Byte

<

ñò

No.

C0018

Switching frequency of the inverter
in ...

^ 41

1 RW

EXT

4

2

8 kHz

... Parameter set 1

2

2

8 kHz

... Parameter set 2

Possible values

0

2 kHz

1

4 kHz

2

8 kHz

C0019

Operating threshold for automatic
brake in ...

1 RW

EXT

4

0

0

{Hz}

20 ... Parameter set 1

2

0

... Parameter set 2

C0022

Rated motor current in ...

^ 61

1 RW

EXT

4

1.0

0

{A}

20.0 ... Parameter set 1

2

1.0

... Parameter set 2

C0024

V/f characteristic – U-boost voltage
in ...

^ 41

1 RW

EXT

4

5.0

1

{%}

25.5 ... Parameter set 1

2

5.0

... Parameter set 2

C0029

V/f characteristic – base frequency
in ...

^ 41

1 RW

EXT

4

50.0

0

{Hz}

120.0 ... Parameter set 1

2

50.0

... Parameter set 2

C0040

RW

4

0

Controller inhibit

0

Controller inhibited

1

Controller enabled

C0043

RW

4

0

Acknowledge fault

0

Action executed

1

Acknowledge fault

C0050

R

4

Current drive frequency

^ 75

0

{Hz}

120.0

C0053

R

4

Current DC−bus voltage

^ 75

0

{V}

1000

C0054

R

4

Current motor current

^ 75

0

{A}

20.0

C0056

R

4

Current output stage temperature

^ 75

0

{°C}

255

C0089

R

4

Frequency inverter − software
version

C0093

R

4

Device type

C0099

R

4

Software version

{xy}

x = main version, y = subversion

C0118

RW

INT

1

10

Configuration of brake resistance
monitoring (WR only with PWD)

10

Resistance 200

W/100 W

30

Resistance 150

W/300 W