Technical data

Rated data

4

l

21

LDEDS−CCU210B EN 4.0

4.2

Rated data

)

Note!

The frequency inverter is not suitable for permanent operation in generator
mode.

Mains voltage

Voltage range

U

N

3/PE/PEN AC 360 V − 0 % ... 528 V + 0 %

Frequency

f

N

45 Hz − 0 % ... 65 Hz + 0 %

Fusing

10 A−T/AC 500 V

Frequency inverter (data for operation on 3/PE/PEN AC 400 V, switching frequency 8 kHz)

Starting current

Effektive

I

eff

[A]

4

Peak

I

peak

[A]

6

Rated power (typical MOC application)

Operating time 70 %

P

N

[kW]

0.75

1.5

Operating time 50 %

P

N

[kW]

2.2

Typical motor power
4−pole asynchronous motor, Y connection

P

N

[kW]

2.2

Max. output power

S

N

[kVA]

1.3

2.0

3.9

Output current

Duration

I

N

[A]

1.8

3.5

5.6

For 60 s

I

max

[A]

3.0

5.0

10

Switching frequency

Optionally

f [kHz]

2, 4, 8

Lenze setting

f [kHz]

8

Motor output frequency

f [Hz]

0 ... 120 variable

Power loss at rated load

P

V

[W]

22

60

100

Power loss in idle state (only half wave
power, 24V−sensors are not connected)

P

V

[W]

6

6

6

DC motor brake control

Brake voltage

Duration (U = U

N

x 0.45)

U [V DC

eff

]

185 (for U

N

= 400 V AC)

Peak (U

peak

= U

N

x

Ö2)

U

peak

[V DC]

564 (for U

N

= 400 V AC)

Max. braking current

I [A

eff

]

0.5 ± 10 %

Integrated switched−mode power supply (supply for external encoders and actuators)

Output voltage

U

A

[V DC]

+24 (21.6 ... 26.4 V DC)

Max. output current
(current−limited)

I

A

[A DC]

0.5

0.7

0.7

Weight

Control system complete, without counter
plug

[approx. kg]

2.8

3.4

5.0