C00637 | resp. to new module in mxi2, C01120 | sync source, C01501 | resp. to comm. error with mxi1 – Lenze E94AYCET User Manual
Page 95: C01120, C01501, Module in slo, 13 parameter reference
Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17
95
13
Parameter reference
13.1
Communication-relevant parameters of the standard device
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
C00637
C01120
C01501
Parameter | Name:
C00637 | Resp. to new module in MXI2
Data type: UNSIGNED_32
Index: 23939 = 0x5D83
Response when a new module has been inserted in module slot 2 of the standard device.
Selection list
(Lenze setting printed in bold)
1 Error
6 Information
5 Warning
4 Warning locked
3 Quick stop by trouble
0 No response
Read access Write access CINH PLC-STOP No transfer
Parameter | Name:
C01120 | Sync source
Data type: UNSIGNED_8
Index: 23455 = 0x5B9F
Selection of the source for DC synchronisation signals.
• Depending on the slot in the standard device, set the selection "4: Module in MXI1" or "5: Module in MXI2" for
the communication module.
• In general, only one source can synchronise the drive.
Synchronisation with "Distributed Clocks" (DC) ( 35)
Selection list
(Lenze setting printed in bold)
0 Off
1 CAN on board
2 CAN module
4 Module in MXI1
5 Module in MXI2
6 Digital input 1
... ...
13 Digital input 8
Read access Write access RSP PLC-STOP No transfer
Scaling factor: 1
Parameter | Name:
C01501 | Resp. to comm. error with MXI1
Data type: UNSIGNED_32
Index: 23074 = 0x5A22
Response to a communication error between an "intelligent" module in module slot 1 and the standard device
Selection list
(Lenze setting printed in bold)
0 No response
1 Error
3 Quick stop by trouble
4 Warning locked
5 Warning
Read access Write access CINH PLC-STOP No transfer