5 external voltage supply, External voltage supply, External voltage supply ( 29) – Lenze E94AYCET User Manual
Page 29: 5installation

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17
29
5
Installation
5.2
Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.5
External voltage supply
The communication module can be supplied externally with voltage via separate supply cables at
the 2-pole plug connector X245.
External voltage supply of the communication module is necessary if the bus communication is to
be continued in the event of a failure of the supply of the standard device.
Access to parameters of a standard device disconnected from the mains is not possible.
Assignment of the X245 plug connector
Terminal data
Note!
With external voltage supply, always use a separate power supply unit, safely separated
to EN 61800-5-1 in every control cabinet (SELV/PELV).
Designation
Description
+
U = 24 V DC (20.4 V -0 % ... 28.8 V +0 %)
I = 130 mA
-
Reference potential for the external voltage supply
Area
Values
Electrical connection
2-pole plug connector (spring connection/screw connection)
Possible connections
Fixed:
1.5 mm
2
(AWG 16)
Flexible:
Without wire end ferrule
1.5 mm
2
(AWG 16)
With wire end ferrule, without plastic sleeve
1.5 mm
2
(AWG 16)
With wire end ferrule, with plastic sleeve
0.5 mm
2
(AWG20)
Starting torque
0.5 ... 0.6 Nm / 4.4 ... 5.3 lb-in (only with screw connection)
Stripping length
6 mm with screw connection
9 mm with spring connection