2 possible causes and remedies, Ethercat: connection to 9400 lost [0x00c83100, Ethercat: memory: no access [0x00c85531 – Lenze E94AYCET User Manual
Page 91: Ethercat: memory: error while reading [0x00c85532, Ethercat: memory: error while writing [0x00c85533, 0x00c83100, 0x00c85114, 0x00c85531, 0x00c85532, 0x00c85533

Lenze · E94AYCET communication module (EtherCAT®) · Communication Manual · DMS 9.0 EN · 02/2014 · TD17
91
12
Error messages
12.2
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
12.2
Possible causes and remedies
This chapter lists all EtherCAT error messages in the numerical order of the error numbers. Possible
causes and remedies as well as responses to the error messages are described in detail.
EtherCAT: Connection to 9400 lost [0x00c83100]
EtherCAT: Internal supply voltage too low [0x00c85114]
EtherCAT: Memory: No access [0x00c85531]
EtherCAT: Memory: Error while reading [0x00c85532]
EtherCAT: Memory: Error while writing [0x00c85533]
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
MXI communication for the Servo Drive 9400 is
interrupted.
• Servo Drive 9400 is switched off.
• The communication module has not been plugged in
properly on the MXI slot of the Servo Drive 9400.
• Switch on Servo Drive 9400.
• Plug in the communication module correctly on the
MXI slot of the Servo Drive 9400.
• Send communication module and Servo Drive 9400
with error description to Lenze.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Voltage loss of the standard device
Check voltage supply.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Access to memory was not possible.
Send communication module with error description to
Lenze.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Parameter could not be read.
Send communication module with error description to
Lenze.
Response (Lenze setting printed in bold)
Setting: not possible
None System fault Fault Trouble Quick stop by trouble Warning locked Warning Information
Cause
Remedy
Parameter could not be written.
Send communication module with error description to
Lenze.