beautypg.com

Commissioning – Lenze 8400 BaseLine Manual User Manual

Page 91

background image

Commissioning

Test commissioning

Test commissioning with terminal control

7

91

EDS84ABD302 EN 4.0

4. Enable controller:
Set terminal X4/RFR to HIGH-Potential (reference: X4/GND).
5. Vary the motor speed or the motor velocity with the potentiometer or by defining

different fixed setpoints:

DI2

DI1

Motor speed

0

0

Setpoint by potentiometer

0

1

40 % of C00011 (reference speed)

1

0

60 % of C00011 (reference speed)

1

1

80 % of C00011 (reference speed)

Internal Keypad

Code

Subcode

Motor speed

-2-

_

`

C...

C051

xxxx

C00051

-

Observe

z

the actual speed value:

C00051

z

appearing messages  92

6. Save the settings with mains failure protection by entering the value ”1” in code

C002, subcode 7.