Strip cables

Strip the control cables (analog and digital) according to the dimensions given in the

following table.

X1

X4

84MOTL_BLC

84MOTL005

X1

X4

[mm

2

]

[AWG]

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVBxE2512

0.2 ... 1.5

24 ... 16

0.2 ... 1.5

24 ... 16

0.5

4.5

E84AVBxE371x
E84AVBxE551x
E84AVBxE751x
E84AVBxE112x
E84AVBxE152x
E84AVBxE222x
E84AVBxE3024

Shield and connect cables

To shield the stripped control cables:
1. Form the cable’s braided shield into a pigtail.
2. Use a wire end ferrule for more stability (optional).
3. Insert the pigtail into one of the screw terminals on X13.
4. Use a suitable screwdriver (see illustration).

X4

X13

84BLGGX004

84BLGGX013

Fig. 6-15