The protective insulation of the ”8400 Inverter Drives” controllers is implemented
according to EN 61800-5-1. The following illustration shows the insulation concept.
X105
X4
X1
X6
X6
X105
X100
X109
X100
X101
EPM
X100
X100
8400BLD005
Fig. 6-1
Electrical isolation between power terminals, control terminals and housing
Legend
Isolation through functional insulation
I
Isolation through basic insulation
II
Safe isolation by double or reinforced insulation
Protection against accidental contact is guaranteed without any further measures.
Range
Connection
Name
Explanation
Power
c
X100
Mains
Safe isolation towards X101 and all control
terminals
X109
DC bus
X105
Motor
X101
Relay contact
Safe isolation towards X100, X105, X109 and all
control terminals
EPM
Memory module
Safe isolation towards other control terminals;
functional insulation towards power terminals
Control
d
X1
System bus (CANopen) Basic insulation towards other control terminals;
safe isolation towards power terminals
X4
Analog IO
Safe isolation towards power terminals
Digital Inputs
Digital output
X6
Diagnostics
Safe isolation towards power terminals