Technical data

Rated data

Operation at rated mains voltage 230 V

4

28

EDS84ABD302 EN 4.0

Operation with external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

c

d

L1, N - laying system

e

L1, N

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84AVBxx2512

C6

6

1.5

-

-

10

14

30

E84AVBxx3712

C6

6

1.5

-

-

10

14

E84AVBxx5512

C10

10

1.5

-

-

10

14

E84AVBxx7512

C10

10

1.5

-

-

10

14

E84AVBxx1122

C16

16

1.5

-

-

15

14

E84AVBxx1522

C20

20

2.5

-

-

20

12

E84AVBxx2222

C25

25

4

4)

-

-

25

10

1)

These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to

VDE 0298-4).

The cable-cross sections apply under the following conditions: Use of PVC-insulated copper cables, conductor

temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, two loaded cores. Smaller cable

cross-sections are not permissible for technical reasons.

2)

Use UL-approved cable, fuses, and fuse holders only.

UL fuse: voltage ≥ 240 V, tripping characteristic ”H”, ”K5” or ”CC”.

The cable cross-sections apply under the following conditions: conductor temperature < 75 °C, ambient temperature

< 45°C. Smaller cable cross-sections are not permissible for technical reasons.

3)

Pulse-current sensitive or universal-current sensitive earth-leakage circuit breaker, short-time delay

If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and

switching frequency.

4)

only with pin-end connector

c

Circuit breaker

d

Fuse

e

Fuse

Observe national and regional regulations