Technical data

General data and operating conditions

4

20

EDS84ABD302 EN 4.0

4

Technical data

4.1

General data and operating conditions

Conformity and approval
Conformity

CE

2006/95/EG

Low-Voltage Directive

Approval

UL

UL 508C

Devices in the power range from 0.25 to 3 kW:

Industrial Control Equipment (IND.CONT.EQ), 5D81, File No.

E170350

Protection of persons and devices
Enclosure

EN 60529

IP 20

in ready-for-use mounted

state

Insulation resistance

EN 61800-5-1

Overvoltage category III

above 2000 m amsl: overvoltage category II

Insulation of control

circuits

EN 61800-5-1

Safe mains isolation by double/reinforced insulation. For

phase to ground (Earth) voltage < 300 VAC

Short-circuit strength

EN 61800-5-1

Motor connection: limited, controller is inhibited, error

acknowledgement is required

Control terminals: full

Protective measures

against

z

Short circuit

z

Earth fault

z

Overvoltage

z

Motor stalling

z

Motor overtemperature

(thermal contact, I

2

t monitoring)

Leakage current

EN 61800-5-1

> 3.5 mA AC, > 10 mA DC

Observe the regulations

and safety instructions!

Cyclic mains switching

Cyclic mains switching at intervals of 3 min is permissible. If

the mains are exceptionally switched three times in one

minute, a pause of 9 min must follow.

Starting current

I

N

Supply conditions
AC mains operation

Direct connection

Power systems

TT

z

For central grounded systems operation is permitted

without restrictions.

z

For corner grounded 400/500 V systems operation is

possible, but reinforced insulation to control circuits is

compromised.

TN

DC-bus operation

Direct connection is possible with E84AVBxxxxx4 devices

Note: When the device is operated from a DC source, the

internal RFI filter is not active and the device is not UL rated.

Motors

EN 60034

Only use motors suitable for inverter operation. Insulation

resistance:

min. û ≥1.5 kV, min. du/dt ≥5 kV/μs