2 display elements and control panel, Commissioning – Lenze 8400 BaseLine Manual User Manual
Page 83
Commissioning
Display elements and control panel
7
83
EDS84ABD302 EN 4.0
7.2
Display elements and control panel
84BLKP0001
Pos. Description
c
4-Character- Display with LEDs (A ... F)
A orange
Set current/torque limit is reached.
B yellow
Minus sign for identifying the negative numbers bigger than 3 characters
C yellow
User-LED- configured with C00621/42.
D red
see table below
E green
F
yellow
Rotational direction CWW
off
Rotational direction CW
blinking
Commanded direction is not equal to actual direction- for example during reversing.
ESC ESC key
Abort of the current operation
↵
Enter key
Confirm and accept changes
Navigation key,
upwards
Short pressing: navigation in the menu level and parameter level and parameter editing
Long pressing (> 2 seconds): fast scrolling function
Navigation key,
downwards
The LEDs ”D” and ”E” have an additional signalling.
LED E
(green)
LED D
(red)
Status
OFF
OFF
→
”Init” state
OFF
→
”ReadyToSwitchOn” state
OFF
→
”SwitchedOn” state
OFF
→
”OperationEnabled” state
→
”Warning” status display
The controller is ready to switch on, switched on or operation is enabled and
there is a warning pending.
OFF
→
”Trouble” state
OFF
→
”Fault” state
OFF
→
”SystemFail” state