4 operation at rated mains voltage 500 v, Operation at rated mains voltage 500 v, Technical data – Lenze 8400 BaseLine Manual User Manual
Page 33: Rated data operation at rated mains voltage 500 v, Alternative dc supply

Technical data
Rated data
Operation at rated mains voltage 500 V
4
33
EDS84ABD302 EN 4.0
4.2.4
Operation at rated mains voltage 500 V
Basis of the data
Mains
Voltage
U
LN
[V]
Voltage range
U
LN
[V]
Frequency range
f [Hz]
3/PE AC
500
400 - 0 % ... 550 + 0 %
45 - 0 % ... 65 + 0 %
Mains current at I
aN
Output power
Motor power
with external mains
choke
without external
mains choke
U, V, W
4 pol. ASM
Type
I
LN
[A]
I
LN
[A]
S
aN
[kVA]
P
aN
[kW]
E84AVBxx3714
1.1
1.5
0.8
0.37
E84AVBxx5514
1.5
2.0
1.1
0.55
E84AVBxx7514
1.9
2.7
1.5
0.75
E84AVBxx1124
2.5
3.6
2.0
1.1
E84AVBxx1524
3.2
4.1
2.4
1.5
E84AVBxx2224
4.3
5.4
3.5
2.2
E84AVBxx3024
5.7
7.2
4.5
3.0
Assignment
Type
Mains choke
E84AVBxx3714
ELN3-1500H003-001
E84AVBxx5514
E84AVBxx7514
E84AVBxx1124
ELN3-0680H006-001
E84AVBxx1524
E84AVBxx2224
E84AVBxx3024
Alternative DC supply
Basis of the data
Mains
Voltage
U
DC
[V]
Voltage range
U
DC
[V]
Frequency range
f [Hz]
2/PE DC
705
565 - 0 % ... 775 + 0 %
-
Type
Input current at I
aN
Output power
U, V, W
Motor power
4.pol. ASM
I
DC
[A]
S
aN
[kVA]
P
aN
[kW]
E84AVBxx3714
1.8
0.8
0.37
E84AVBxx5514
2.4
1.1
0.55
E84AVBxx7514
3.1
1.5
0.75
E84AVBxx1124
4.4
2.0
1.1
E84AVBxx1524
5.0
2.4
1.5
E84AVBxx2224
6.6
3.5
2.2
E84AVBxx3024
8.6
4.5
3.0