Installation according to EMC (installation of a CE-typical drive system)

Detecting and eliminating EMC interferences

6

59

EDS84ABD302 EN 4.0

6.2.7

Detecting and eliminating EMC interferences

Fault

Cause

Remedy

Interferences to analog

setpoints of devices and

measuring systems

Unshielded motor cable

Use shielded motor cable

Contact surface of shield is too small

Provide optimum shielding according to

instructions

Shield of the motor cable is interrupted

by terminal strips, switches etc.

z

Keep components separated from all

other parts by at least 100mm

z

Use motor choke

Additional, unshielded cables are

installed within the motor cable (e.g. for

motor temperature monitoring)

Separate the additional cables and shield

them

Unshielded motor cable ends too long

Shorten unshielded cable ends to

maximally 40 mm

Conducted interference

level is exceeded on the

supply side

Terminal strips for the motor cable are

directly installed next to the supply

terminals

Keep the terminals strips for the motor

cable separated from the supply and

other control terminals by at least 100

mm

Painted mounting plate

Optimise PE connection:

z

Remove paint

z

Use zinc-coated mounting plate

HF short circuit

Check cable routing