Technical data

Rated data

Operation at rated mains voltage 230 V

4

27

EDS84ABD302 EN 4.0

Output currents [A] at switching frequency

2 kHz

4 kHz

8 kHz

16 kHz

Type

I

aN2

I

aM2

I

aN4

I

aM4

I

aN8

I

aM8

I

aN16

I

aM16

E84AVBxx2512

1.7

3.4

1.7

3.4

1.7

3.4

1.1

2.2

E84AVBxx3712

2.4

4.8

2.4

4.8

2.4

4.8

1.6

3.2

E84AVBxx5512

3.0

6.0

3.0

6.0

3.0

6.0

2.0

4.0

E84AVBxx7512

4.0

8.0

4.0

8.0

4.0

8.0

2.7

5.4

E84AVBxx1122

5.5

11.0

5.5

11.0

5.5

11.0

3.7

7.4

E84AVBxx1522

7.0

14.0

7.0

14.0

7.0

14.0

4.7

9.4

E84AVBxx2222

9.5

19.0

9.5

19.0

9.5

19.0

6.3

12.6

I

aNx

Rated value - continuous output current

I

aMx

Maximum output current (overload current)

z

Periodic load change of 3 s with I

aMx

and recovery time of 12 s with 75 % I

aNx

z

Can be achieved with the setting ”x kHz fixed/...” in C00018

Switching

frequency

When the maximum heatsink temperature is reached, the switching frequency

is reduced to 4 kHz.
With the setting ”x kHz var./...” in C00018, the switching frequency is reduced

dynamically.

z

At 16 kHz and Ia > 100 % x IaN8 to 8 kHz

z

At 8 kHz and Ia > 150 % x IaN8 to 4 kHz

Fuses and cable cross-sections

Operation without external mains choke/mains filter
Type

Installation according to EN 60204-1

1)

Installation according

to UL

2)

FI

3)

c

d

L1, N - laying system

e

L1, N

B2

C

F

[A]

[A]

[mm

2

]

[mm

2

]

[mm

2

]

[A]

[AWG]

[mA]

E84AVBxx2512

C10

10

1.5

-

-

10

14

30

E84AVBxx3712

C10

10

1.5

-

-

10

14

E84AVBxx5512

C16

16

1.5

-

-

12

14

E84AVBxx7512

C16

16

1.5

-

-

15

14

E84AVBxx1122

C20

20

2.5

-

-

20

12

E84AVBxx1522

C25

25

4

4)

-

-

20

10

E84AVBxx2222

C32

32

6

4)

-

-

35

10

1)

These values are recommendations only. Other dimensioning values/laying systems are possible (e.g. according to

VDE 0298-4).

The cable-cross sections apply under the following conditions: Use of PVC-insulated copper cables, conductor

temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, two loaded cores. Smaller cable

cross-sections are not permissible for technical reasons.

2)

Use UL-approved cable, fuses, and fuse holders only.

UL fuse: voltage ≥ 240 V, tripping characteristic ”H”, ”K5” or ”CC”.

The cable cross-sections apply under the following conditions: conductor temperature < 75 °C, ambient temperature

< 45°C. Smaller cable cross-sections are not permissible for technical reasons.

3)

Pulse-current sensitive or universal-current sensitive earth-leakage circuit breaker, short-time delay

If cables are longer than 50 m, the protective circuit-breaker may respond, depending on the cable type and

switching frequency.

4)

only with pin-end connector

c

Circuit breaker

d

Fuse

e

Fuse

Observe national and regional regulations