Overcurrent operation
Operation at rated mains voltage 500 V
4
36
EDS84ABD302 EN 4.0
4.3
Overcurrent operation
The controllers are designed for a time-limited overcurrent. The ”Ixt” protective function
protects the controller against impermissible overloads. The protective function monitors
the output current within two different time periods.
Definition of the cycles:
ƒ
15-s cycle c
– 3 s load period with peak current
– 12 s recovery time with limited current
ƒ
180-s cycle d
– 60 s load period with peak current
– 120 s recovery time with limited current
A load period with peak current must be followed by a recovery time. During the recovery
time, the current must not exceed the given value. The utilisation detected in the cycles
must not exceed 100% IaN8, otherwise a warning signal is displayed.
The given values refer to the rated output current I
aN8
.
t
0
100
2
0
1
I
[%]
aN8
3
3 s
12 s
60 s
120 s
8400IZ180
Fig. 4-1
Overcurrent capacity in 230/400 V operation at 45° C
Peak current for 3 s
c
15-s cycle
max. current in recovery time for 12 s
Peak current for 60 s
d
180-s cycle
max. current in recovery time for 120 s