Electrical installation

Devices in the power range from 0.37 to 3 kW (3/PE AC 400 V)

Terminal assignment of the power connections

6

70

EDS84ABD302 EN 4.0

Motor connection

Terminal X105

Labelling

Description

U, V, W

Motor

PE

PE conductor

84BDGG012

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVBxE3714

1 ... 2.5

18 ... 12

0.5

4.5

3.5 x 0.6

E84AVBxE5514
E84AVBxE7514
E84AVBxE1124
E84AVBxE1524
E84AVBxE2224
E84AVBxE3024

Connection of external brake resistor

X109

84BLDGG020

Fig. 6-14

Inserting terminal X109

Before plugging in the terminal X109:
1. Switch off the controller and wait for at least 3 minutes before start working.
2. Make sure that there is no residual voltage.
3. Pull the cover carefully to the side without removing it completely.
4. Plug in the terminal.