Technical data – Lenze 8400 BaseLine Manual User Manual
Page 22
Technical data
General data and operating conditions
4
22
EDS84ABD302 EN 4.0
EMC (when installed and connected per section 5.2)
Noise emission
conducted
EN 61800-3
up to 25 m of shielded motor cable: category C2
radiated
Category C2 with proper cable grounding and enclosure
Noise immunity inside grounded enclosure (according to requirements of EN 61800-3)
Electrostatic discharge
(ESD)
EN 61000-4-2
8 kV with air discharge,
4 kV with contact discharge against enclosure
Radio frequency
conducted
EN 61000-4-6
150 kHz ... 80 MHz, 10 V/m 80 % AM (1kHz)
radiated (enclosure)
EN 61000-4-3
80 MHz ... 1000 MHz, 10 V/m 80 % AM (1kHz)
Burst
Power terminals and
interfaces
EN 61000-4-4
2 kV/5 kHz
Signal interfaces
EN 61000-4-4
1 kV/5 kHz
Control terminals
EN 61000-4-4
2 kV/5 kHz
Surge
Power terminals
EN 61000-4-5
1.2/50 μs,
1 kV phase/phase, 2 kV phase/PE
Control terminals
EN 61000-4-5
1.2/50 μs, 1 kV
Operation on public supply
systems
EN 61000-3-2
EN 61000-3-12
The devices are intended for use in an industrial
environment. When being used on public network,
additional measures must be taken to limit the expected
radio interference. The compliance with the requirements for
the machine/plant is the responsibility of the manufacturer
of the machine or system!
EN 61000-3-2
< 0.5 kW: with mains choke
0.5 ... 1 kW: with active filter
> 1 kW at mains current ≤ 16 A: No limit values for harmonic
currents
EN 61000-3-12
Mains current > 16 A: further measures are required for
compliance with the standard