Technical data

General data and operating conditions

4

22

EDS84ABD302 EN 4.0

EMC (when installed and connected per section 5.2)
Noise emission

conducted

EN 61800-3

up to 25 m of shielded motor cable: category C2

radiated

Category C2 with proper cable grounding and enclosure

Noise immunity inside grounded enclosure (according to requirements of EN 61800-3)

Electrostatic discharge

(ESD)

EN 61000-4-2

8 kV with air discharge,

4 kV with contact discharge against enclosure

Radio frequency

conducted

EN 61000-4-6

150 kHz ... 80 MHz, 10 V/m 80 % AM (1kHz)

radiated (enclosure)

EN 61000-4-3

80 MHz ... 1000 MHz, 10 V/m 80 % AM (1kHz)

Burst

Power terminals and

interfaces

EN 61000-4-4

2 kV/5 kHz

Signal interfaces

EN 61000-4-4

1 kV/5 kHz

Control terminals

EN 61000-4-4

2 kV/5 kHz

Surge

Power terminals

EN 61000-4-5

1.2/50 μs,

1 kV phase/phase, 2 kV phase/PE

Control terminals

EN 61000-4-5

1.2/50 μs, 1 kV

Operation on public supply

systems

EN 61000-3-2

EN 61000-3-12

The devices are intended for use in an industrial

environment. When being used on public network,

additional measures must be taken to limit the expected

radio interference. The compliance with the requirements for

the machine/plant is the responsibility of the manufacturer

of the machine or system!

EN 61000-3-2

< 0.5 kW: with mains choke
0.5 ... 1 kW: with active filter
> 1 kW at mains current ≤ 16 A: No limit values for harmonic

currents

EN 61000-3-12

Mains current > 16 A: further measures are required for

compliance with the standard