Technical data

Rated data

Operation at rated mains voltage 400 V

4

29

EDS84ABD302 EN 4.0

4.2.3

Operation at rated mains voltage 400 V

Basis of the data

Mains

Voltage

U

LN

[V]

Voltage range

U

LN

[V]

Frequency range

f [Hz]

3/PE AC

400

320 - 0 % ... 440 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Output power

Motor power

with external mains

choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LN

[A]

I

LN

[A]

S

aN

[kVA]

P

aN

[kW]

E84AVBxx3714

1.4

1.8

0.8

0.37

E84AVBxx5514

1.8

2.3

1.2

0.55

E84AVBxx7514

2.2

3.2

1.6

0.75

E84AVBxx1124

3.2

4.2

2.1

1.1

E84AVBxx1524

3.6

4.7

2.5

1.5

E84AVBxx2224

5.0

6.2

3.6

2.2

E84AVBxx3024

7.1

10.2

4.8

3.0

Assignment
Type

Mains choke

E84AVBxx3714

ELN3-1500H003-001

E84AVBxx5514
E84AVBxx7514
E84AVBxx1124

ELN3-0680H006-001

E84AVBxx1524
E84AVBxx2224
E84AVBxx3024

ELN3-0250H013-001