beautypg.com

Electrical installation – Lenze 8400 BaseLine Manual User Manual

Page 64

background image

Electrical installation

Devices in the power range 0.25 ... 2.2 kW (1/N/PE AC 230 V)

Terminal assignment of the power connections

6

64

EDS84ABD302 EN 4.0

DC bus

X109

84BLDGG020

Fig. 6-10

Inserting terminal X109

Before plugging in the terminal X109:
1. Switch off the controller and wait for at least 3 minutes before start working.
2. Make sure that there is no residual voltage.
3. Pull the cover carefully to the side without removing it completely.
4. Plug in the terminal.

Terminal X109

Labelling

Description

-UG

RB

1)

+ UG

DC bus for connecting devices operating at 230 V to an external

brake module, DC bus system or DC supply (only with devices in

the power range from 0.25 to 1.5 kW)

84BDGG109

1)

not connected

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVBxE2512

0.5 ... 1.5

22 ... 16

0.5

4.5

3.5 x 0.6

E84AVBxE3712
E84AVBxE5512
E84AVBxE7512
E84AVBxE1122
E84AVBxE1522
E84AVBxE2222