Technical data
General data and operating conditions
4
21
EDS84ABD302 EN 4.0
Environmental conditions
Climate
Storage
IEC/EN 60721-3-1
1K3 (-25 ... +60 °C)
Transport
IEC/EN 60721-3-2
2K3 (-25 ... +70 °C)
Operation
IEC/EN 60721-3-3
3K3 (-10 ... +55 °C)
Operation at 2/4 kHz, +45 ... +55 °C:
Operation at 8/16 kHz, +40 ... +55 °C:
For operation above +40 ... +45°C, reduce rated output
current by 2.5 %/°C
Site altitude
0 ... 4000 m amsl
1000 ... 4000 m amsl:
Reduce rated output current by 5 %/1000 m
2000 ... 4000 m amsl: overvoltage category II
Pollution
EN 61800-5-1
Pollution Degree 2
Vibration resistance
(9.81 m/s
2
= 1 g)
Transport
IEC/EN 60721-3-2
2M2
EN 61800-5-1
2 ... 9 Hz: amplitude 3.5 mm
10 ... 200 Hz: acceleration resistant up to 10 m/s
2
200 ... 500 Hz: acceleration resistant up to 15 m/s
2
Operation
Germanischer Lloyd
5 ... 13,2 Hz: amplitude ±1 mm
13.2 ... 100 Hz: acceleration resistant up to 0.7 g
EN 61800-5-1
10 ... 57 Hz: amplitude 0.075 mm
57 ... 150 Hz: acceleration resistant up to 10 m/s
2
(1 g)
Requirements on the motor cable
Capacitance per unit length
≤
1.5 mm
2
/AWG 16
C
Core/core
/C
Core/shield
≤
75/150 pF/m
≥
2.5 mm
2
/AWG 12
C
core/core
/C
Core/shield
≤
100/≤ 150 pF/m
Electric strength
VDE 0250-1
U
0
/U
=
0.6/1.0 kV
(U
0
= r.m.s. value - external conductor to PE,
U = r.m.s. value - external conductor to external conductor)
UL
U ≥ 600 V
(U = r.m.s. value - external conductor to external conductor)