Mechanical installation, 1 important notes – Lenze 8400 BaseLine Manual User Manual
Page 43
Mechanical installation
Important notes
5
43
EDS84ABD302 EN 4.0
5
Mechanical installation
5.1
Important notes
Danger!
Sticker with warning note must be displayed prominently and close to the
device!
Note!
The devices must be installed in housings (e.g. control cabinets) to meet
applicable regulations.
ƒ
If the cooling air is polluted (lint, (conductive) dust, soot, aggressive gases), take
adequate countermeasures, as e.g.:
– Separate air guide
– Installation of filters
– Regular cleaning of the filters
ƒ
Possible mounting position:
– Vertical on the mounting plate (mains connections at the top, motor connection at
the bottom)
ƒ
Maintain the specified free spaces above and below the controller to other
installations!
– Ensure unimpeded ventilation of cooling air and outlet of exhaust air.
– You can install several controllers of the 8400 L-force Inverter Drives product range
next to each other without any clearance in the control cabinet.
ƒ
The mounting plate of the control cabinet must be electrically conductive.
ƒ
In case of continuous vibrations or shocks use vibration dampers.