Electrical installation

Devices in the power range from 0.37 to 3 kW (3/PE AC 400 V)

Terminal assignment of the power connections

6

69

EDS84ABD302 EN 4.0

Connection to the DC bus (+U

G

, -U

G

)

X109

84BLDGG020

Fig. 6-13

Inserting terminal X109

Before plugging in the terminal X109:
1. Switch off the controller and wait for at least 3 minutes before start working.
2. Make sure that there is no residual voltage.
3. Pull the cover carefully to the side without removing it completely.
4. Plug in the terminal.

Terminal X109

Labelling

Description

- UG

RB

+ UG

DC bus for connecting devices operating at 400 V to a

DC bus system or DC supply.

84BDGG109

Terminal data

Max. conductor cross-section

Tightening torque

[mm

2

]

[AWG]

[Nm]

[lb-in]

E84AVBxE3714

0.5 ... 1.5

22 ... 16

0.5

4.5

3.5 x 0.6

E84AVBxE5514
E84AVBxE7514
E84AVBxE1124
E84AVBxE1524
E84AVBxE2224
E84AVBxE3024