Technical data

Rated data

Operation at rated mains voltage 230 V

4

26

EDS84ABD302 EN 4.0

4.2.2

Operation at rated mains voltage 230 V

Basis of the data

Mains

Voltage

U

LN

[V]

Voltage range

U

LN

[V]

Frequency range

f [Hz]

1/N/PE AC

230

180 - 0 % ... 264 + 0 %

45 - 0 % ... 65 + 0 %

Mains current at I

aN

Output power

Motor power

with external mains

choke

without external

mains choke

U, V, W

4 pol. ASM

Type

I

LN

[A]

I

LN

[A]

S

aN

[kVA]

P

aN

[kW]

E84AVBxx2512

3.0

3.4

0.6

0.25

E84AVBxx3712

4.2

5.1

0.9

0.37

E84AVBxx5512

5.4

6.7

1.1

0.55

E84AVBxx7512

7.0

8.8

1.4

0.75

E84AVBxx1122

9.9

12.0

2.0

1.1

E84AVBxx1522

11.8

13.7

2.5

1.5

E84AVBxx2222

15.7

22.0

3.4

2.2

Assignment
Type

Mains choke

E84AVBxx2512

ELN1-0900H005

E84AVBxx3712
E84AVBxx5512

ELN1-0500H009

E84AVBxx7512
E84AVBxx1122

ELN1-0250H018

E84AVBxx1522
E84AVBxx2222