AS-i 3.0 Command Interface

Command Interface Examples

Subject to reasonable modifications due to technical advances

Id.-No.: 102875 Issue date - 3.12.2007

EUCHNER GmbH + Co. KG

Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen

Tel. +49/711/7597-0, Fax +49/711/753316

81

No result because toggle bit = 0.

Set the toggle bit:

The master is now in configuration mode.

Result: See chapter 4 "Commands of the Command Interface".

2. Write single configuration to master

Writing a configuration of an AS-i slave to the master.

For example:

16 bit input 4 CH at address 4 (Slave data sheet)

ID: 3

hex

ID2: E

hex

IO:

7

hex

ID1: F

hex

Response

Byte 1

00

hex

(or old values)

Byte 2

00

hex

(or old values)

Byte 3

00

hex

(or old values)

Byte 4

00

hex

(or old values)

Byte 12

00

hex

(or old values)

Request: SET_OP_MODE

Byte 1

0C

hex

(SET_OP_MODE)

Byte 2

80

hex

(T = 1, master 1, single master)

Byte 3

01

hex

(= config mode)

Byte 4

00

hex

Byte 12

00

hex

Response

Byte 1

0C

hex

Byte 2

80

hex

(T = 1, result = 0)

Byte 3

00

hex

(or old values)

Byte 4

00

hex

(or old values)

Byte 12

00

hex

(or old values)