2 slave list without ecflags, 2 "safety at work" monitor diagnosis, Slave list without ecflags – EUCHNER AS-i 3.0 Command Interface User Manual
Page 64: Safety at work" monitor diagnosis
AS-i 3.0 Command Interface
Commands of the Command Interface
Subject to reasonable modifications due to technical advances
Id.-No.: 102875 Issue date - 3.12.2007
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen
Tel. +49/711/7597-0, Fax +49/711/753316
64
1 safety slave with unreleased safety function,
AS-inferface address 5.
Reponse: 7E 00 01 25 10 04 00 00
4.7.1.2
Slave list without EcFlags
(Function: 0D
16)
There is a function 0D
16
in addition to the function 00
16
. The function 0D
16
has no
EcFlags in the response. The response falls short for 2 bytes.
4.7.2
"Safety at Work" Monitor diagnosis
Function: 02
16
Since the "Safety at Work" monitor can generate more than 32 Byte diagnosis da-
ta, these must be read with several command interface calls. The byte 5 declares
the start index in the field of the diagnosis data.
If the start index is 0, new data is fetched from the monitor. Otherwise, the function
will respond out of the memory; the data can be read consistently.
Request
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7E
16
2
T
O
circuit
3
0Dh
Response (by O
≡ 0)
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7E
16
2
T
response
3
7
6
5
4
3
2
1
–
4
15
14
13
12
11
10
9
8
5
23
22
21
20
19
18
17
16
6
31
30
29
28
27
26
25
24
Response (by O
≡ 1)
Byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
7E
16
2
T
response
3
–
1
2
3
4
5
6
7
4
8
9
10
11
12
13
14
15
5
16
17
18
19
20
21
22
23
6
24
25
26
27
28
29
30
31