AS-i 3.0 Command Interface
Commands of the Command Interface
Subject to reasonable modifications due to technical advances
Id.-No.: 102875 Issue date - 3.12.2007
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16, D-70771 Leinfelden-Echterdingen
Tel. +49/711/7597-0, Fax +49/711/753316
49
4.5.10
Write parameter (WRITE_P)
The AS-i slave parameter value transferred with the command is passed on to the
addressed AS-i slave.
The parameter is stored in the AS-i Master only temporarily and is not stored as a
configured parameter in the EEPROM!
The AS-i slave transfers its current parameter value in the response (parameter
echo). This can deviate from the value that has just been written according to the
AS-i master specification.
Meaning of bit B:
B = 0 Single AS-i slave or A-slave
B = 1 B-slave
4.5.11
Read parameter (READ_PI: Read_Parameter)
This call returns the current parameter value (actual parameter) of an AS-i slave
sent by the AS-i Master. This value must not be confused with the parameter echo
that is supplied by the AS-i slave as a response to the write_p job.
This command can not be used for a directly reading of an AS-i parameter out of
an AS-i slave.
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
02
16
2
T
–
circuit
3
–
B
slave address
4
–
parameter
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
02
16
2
T
result
3
–
slave response
Request
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
03
16
2
T
–
circuit
3
–
B
slave address
Response
byte
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
1
03
16
2
T
result
3
–
PI