Valve Motor Drive Control

Type: VMD Controller Definition

Valve Motor Drive Controllers are designed to control Modulating Valves using a special “Open
Loop” Valve Motor Drive (VMD) PI control algorithm. Output signals are provided to move the valve
further open, or further closed when the process is higher or lower than the desired setpoint. When
on setpoint, no output is required to maintain control unless load conditions change. This known as
Three-Point Stepping control.
Valve Position or Flow Indication is possible if an Auxiliary Input option module has been fitted and
configured for this purpose.
Also refer to

Auxiliary Input

,

Modulating Valve

,

Open Loop VMD

,

PI Control

,

PID

,

Setpoint

and

Valve Position Indication

.

Valve Position or Flow Indication

Type: VMD Controller Definition

The Valve Motor Drive Controllers do not require any kind of position feedback in order for the PID
algorithm to correctly control the process. However, where feedback or flow level signals are
available, they can be displayed as a percentage (

0000

to

100

100

100

100

) of the possible valve opening or flow

level. Valve Position Indication is shown in the Operator Mode lower display in place of the Setpoint
when the Display Strategy is set to

7

.

Valve Position Feedback is usually provided by means of a potentiometer linked to the valve.
Potentiometers can be directly connected to the Full Auxiliary Input (Option Slot B only).
Flow meters typically have linear 0-20/4-20mA or 0-5/0-10V signals, which can be used with either
the Full Auxiliary Input or the Basic Auxiliary Input (Option Slot A only) of the

1

/

16

Din VMD

Controllers.
Even when position feedback is provided in this way, the information is not used by the Open Loop
VMD control algorithm when positioning the valve, avoiding problems associated with faulty
feedback signals.
Also refer to

Auxiliary Input

,

Display Strategy

,

Open Loop VMD

,

PID

, Set Valve Closed Position,

Set Valve Open Position, Setpoint, and Valve Motor Control.

Valve Open Limit

Type: VMD Controller Parameter

When Valve Position Indication is to be used on Valve Motor Controllers, this parameter
provides a “clamp” on the upper valve position, which the controller will not attempt to drive the valve
past. It can be set between

100

100

100

100

(fully open) and the Valve Closed Limit value +1, expressed as a

percentage of the valve’s “fully open” position.
The Auxiliary Input must correctly scaled using the Set Valve Open and Closed parameters before
using this parameter.
Display code =

PiLL

, default setting =

100

100

100

100

.

Also refer to

Auxiliary Input

,

Set Valve Closed Position

,

Set Valve Open Position

,

Valve Close

Limit

,

Valve Motor Control

and

Valve Position Indication

.

VMD

Type: VMD Controller Parameter

- Refer to

Valve Motor Control

.