Despatch P1400+ Temperature Controller User Manual
Page 41
35
Parameter
Lower
Display
Upper
Display
Description
Default
Value
When
Visible
2_10
2 to 10V DC
Scale Range
Upper Limit
ruL
Scale Range Lower Limit +100 to Range
Max
Linear
inputs =
1000
(°C/°F
inputs =
max
range)
Always
Scale Range
Lower Limit
rLL
Range Min. to Scale range Upper Limit -
100
Linear = 0
(°C/°F =
min range)
Always
0
1
2
Decimal point
position
dPoS
3
Decimal point position in
non-temperature ranges.
0 = XXXX
1 = XXX.X
2 = XX.XX
3 = X.XXX
1
Inpt =
mV,
V or mA
SnGL
Primary control
Control Type
CtYP
duAL
Primary and Secondary
control (e.g. for heat & cool)
SnGL
Always
reu
Reverse Acting
Primary Output
Control Action
CtRL
dir
Direct Acting
reu
Always
P_Hi
Process High Alarm
P_Lo
Process Low Alarm
dE
Deviation Alarm
bAnd
Band Alarm
Alarm 1Type
ALA1
nonE
No alarm
P_Hi
Always
Process High
Alarm 1 value*
PhA1
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Max.
ALA1 =
P_Hi
Process Low
Alarm 1 value*
PLA1
Range Min. to Range Max
Parameter repeated in Setup Mode
Range
Min.
ALA1 =
P_Lo
Deviation
Alarm 1 Value*
dAL1
±
span from setpoint
Parameter repeated in Setup Mode
5
ALA1 =
dE
Band Alarm 1
value*
bAL1
1 LSD to full span from setpoint.
Parameter repeated in Setup Mode
5
ALA1 =
bAnd
Alarm 1
Hysteresis*
AHY1
1 LSD to 100% of span (in display units)
on “safe” side of alarm point.
Parameter repeated in Setup Mode
1
Always
Alarm 2 Type
ALA2
As for alarm 1 type
P_Lo
Always
Process High
Alarm 2 value*
PhA2
Range Min. to Range Max.
Parameter repeated in Setup Mode
Range
Max.
ALA2 =
P_Hi