Set Valve Opened Position

Type: VMD Controller Parameter

When Valve Position Indication is to be used on Valve Motor Controllers, this parameter defines the
input value that will be measured by the Auxiliary Input, when the valve is fully opened. The valve
must driven to its “Open” end stop before setting this parameter.
It must not be used to limit valve movement, separate Valve Close and Open Limit parameters are
available for this purpose.
Display code =

PcLL

, default setting = Auxiliary Input Range Maximum.

Also refer to

Auxiliary Input

,

Set Valve Closed Position

,

Valve Close Limit

,

Valve Open Limit

,

Valve Motor Control

and

Valve Position Indication

.

Setpoint

Type: Controller Definition

The target value at which a controller will attempt to maintain the process variable by adjusting its
power output level. Controllers can have either one or two setpoints. These can be one or two local
internal setpoints (

SP

or

SP1

and

SP2

), or one local internal setpoint (

LSP

) and one externally

adjusted remote (

RSP

) setpoint, if a Remote Setpoint module is fitted. The value of the setpoints can

be adjusted between the Setpoint Upper Limit and Setpoint Lower Limits. The active setpoint is
defined by the status of the Setpoint Select parameter or a digital input.
Also refer to

Limit Setpoint

,

Process Variable

,

Remote Setpoint

,

Scale Range Lower Limit

,

Setpoint Lower Limit

,

Setpoint Upper Limit

and

Setpoint Select

Setpoint Upper Limit

Type: Controller Parameter

The maximum limit allowed for operator setpoint adjustments. It should be set to keep the setpoint
below a value that might cause damage to the process. The adjustment range is between Scale
Range Upper Limit and Scale Range Lower Limit. The value cannot be moved below the current
value of the setpoint.
Display code =

SPuL

, default value is Scale Range Upper Limit.

Also refer to

Scale Range Lower Limit

,

Scale Range Upper Limit

,

Setpoint

and

Setpoint Lower

Limit

.

Setpoint Lower Limit

Type: Controller Parameter

The minimum limit allowed for operator setpoint adjustments. It should be set to keep the setpoint
above a value that might cause damage to the process. The adjustment range is between Scale
Range Lowe Limit and Scale Range Upper Limit. The value cannot be moved above the current
value of the setpoint.
Display code =

SPLL

, default value = Scale Range Lower Limit.

Also refer to

Scale Range Lower Limit

,

Scale Range Upper Limit

,

Setpoint

and

Setpoint Upper

Limit

.

Setpoint Ramping Enable

Type: Controller Parameter

Enables or disables the viewing and adjustment of the Setpoint Ramp Rate in Operator Mode. This
parameter does not disable the ramping SP feature; it merely removes it from Operator Mode. It can
still be viewed and adjusted in Setup Mode. To turn off ramping, the ramp rate must be set to OFF
(blank).
Display code =

SPr

, default setting = Disabled.

Also refer to

Process Variable

,

Setpoint

and

Setpoint Ramp Rate

.

Setpoint Ramp Rate

Type: Controller Parameter

The rate at which the actual setpoint value will move towards its target value, when the setpoint
value is adjusted or the active setpoint is changed. With ramping in use, the initial value of the actual