Table 7.

Automatic Tune Mode Parameters

Parameter

Upper Display
Adjustment Range

Lower

Display

Default

Value

When

Visible

Pre-tune

On

or

OFF.

Indication remains

OFF

if Pre-Tune

cannot be used at this time. This
applies if:
a). The setpoint is ramping
b). The process variable is less than
5% of span from the setpoint
c). The primary or secondary output
proportional bands = 0

Ptun

OFF

Controller

models only

Self-tune

On

or

OFF

.

Indication remains

OFF

if Self-Tune

cannot be used at this time. This
applies if either proportional band = 0.

Stun

OFF

Controller

models only

Automatic tune
mode lock code

0 to 9999

tLoc

0

Controller

models only

7.3 Product Information Mode

This is a read only mode describing the instrument and the options fitted to it.

Navigating in the Product Information Mode

Press to view each parameter in turn.

Hold Down and press to return to

Select Mode

.

Note:
If there is no key activity for 2 minutes the controller automatically returns to operator mode

Table 8.

Product Information Mode Parameters

Parameter Possible Values

Upper/Main

Display

Lower

Display

Input type

Universal input

Uni

In_1

No option fitted

nonE

Relay

rLY

SSR drive

SSr

Triac

tri

Option 1
module type

Linear voltage / current output

Lin

OPn1