3 product information mode – Despatch P1400+ Temperature Controller User Manual
Page 35

29
Table 7.
Automatic Tune Mode Parameters
Parameter
Upper Display
Adjustment Range
Lower
Display
Default
Value
When
Visible
Pre-tune
On
or
OFF.
Indication remains
OFF
if Pre-Tune
cannot be used at this time. This
applies if:
a). The setpoint is ramping
b). The process variable is less than
5% of span from the setpoint
c). The primary or secondary output
proportional bands = 0
Ptun
OFF
Controller
models only
Self-tune
On
or
OFF
.
Indication remains
OFF
if Self-Tune
cannot be used at this time. This
applies if either proportional band = 0.
Stun
OFF
Controller
models only
Automatic tune
mode lock code
0 to 9999
tLoc
0
Controller
models only
7.3 Product Information Mode
This is a read only mode describing the instrument and the options fitted to it.
Navigating in the Product Information Mode
Press to view each parameter in turn.
Hold Down and press to return to
Select Mode
.
Note:
If there is no key activity for 2 minutes the controller automatically returns to operator mode
Table 8.
Product Information Mode Parameters
Parameter Possible Values
Upper/Main
Display
Lower
Display
Input type
Universal input
Uni
In_1
No option fitted
nonE
Relay
rLY
SSR drive
SSr
Triac
tri
Option 1
module type
Linear voltage / current output
Lin
OPn1