8.5 Manual Control Mode

To allow manual control to be selected in Operator Mode,

poen

must be enabled in Set Up Mode.

Manual Mode can be selected using the front keys or by use of a digital input if one has been fitted
and configured for this function.

Selecting/deselecting Manual Control Mode

Press the key to toggle between Automatic and Manual control.

The indicator flashes continually in Manual Mode

Press or to adjust the output power to the required value.

CAUTION:

The Manual Mode power level can be adjusted from 0 to 100% (-100 to +100% for dual
output). It is not restricted by the Output Power Limit parameter

OPuL

.


Note:
Disabling

poen

in Set Up Mode while manual control mode is active will lock the controller into

manual mode. Pressing the Auto/Man key will no longer cause a return to automatic control. To
exit from Manual Mode,

poen

must temporarily be re-enabled.

8.6 1400+ Controllers –Communications Parameters

The Modbus parameter addresses, and the possible ASCII message types and parameter indents
for the 1400+ are detailed below. RO indicates a parameter is read only, R/W indicates it can also
be written to. Communications writes will not implemented if the Communications Write Parameter is
disabled. Refer to the Modbus and ASCII Communications sections of this manual for details of the
protocols used.

Bit Parameters

Bit parameters are not applicable to the ASCII protocol.

Table 13.

1400+ Communications - Bit Parameters

Parameter

Modbus

Parameter No.

Notes

Communication
Write Status

1

RO

1 = Write Enabled, 0 = Write Disabled. A negative
acknowledgement (exception code 3) is sent to write
commands if communications writes are disabled

Auto / Manual

2

R/W

1 = Manual Control, 0 = Automatic Control

Self Tune

3

R/W

1 = Activate(d), 0 = Dis-engage(d)

Pre tune

4

R/W

1 = Activate(d), 0 = Dis-engage(d)