Despatch P1400+ Temperature Controller User Manual

Page 44

background image

38

Parameter

Lower
Display

Upper
Display

Description

Default

Value

When
Visible

1111

.

2222

1.2 kbps

2222

.

4444

2.4 kbps

4444

.

8888

4.8 kbps

9999

.

6666

9.6 kbps

Bit rate

bAud

19

19

19

19

.

2222

19.2 kbps

4444

.

8888

OpnA = r
485

Communica-
tions Address

Addr

1111

Unique address assigned to
the instrument in the range
of 1 to 255 (Modbus),
1 to 99 (Ascii)

1111

OpnA =
r485

r_

o

Read only. Comms
writes ignored

Communica-
tions Write
Enable

CoEn

r_

W

Read / Write. Writing via
Comms is possible

r_ W

Always

diS1

Setpoint 1 / Setpoint 2
Select**

Digital Input 1
Usage

diGi

diAs

Automatic / Manual
Select**

diS1

OpnA =
diGi

diS1

Setpoint 1 / Setpoint 2
Select**

diAs

Automatic / Manual
Select**

Digital Input 2
Usage

diG2

dirs

Remote / Local Setpoint
Select

dirS

Opnb =
rSPi

0_20

0_20

0_20

0_20

0 to 20mA DC input

4_20

4_20

4_20

4_20

4 to 20mA DC input

0_10

0_10

0_10

0_10

0 to 10V DC input

2_10

2_10

2_10

2_10

2 to 10V DC input

0_5

0_5

0_5

0_5

0 to 5V DC input

1_5

1_5

1_5

1_5

1 to 5V DC input

OpnA

or

Opnb =
rSPi

100

100

100

100

0 to 100mV DC input

Remote
Setpoint Input
Range

rinP

Pot

Potentiometer (

2K

Ω)

0_10

Opnb =
rSPi

Remote
Setpoint Upper
Limit

rSPu

−1999

−1999

−1999

−1999

to

9999

9999

9999

9999

RSP value to be used when RSP input is
at maximum.

Range
max

OpnA =
rSPi

Remote
Setpoint Lower
Limit

rSPL

−1999

−1999

−1999

−1999

to

9999

9999

9999

9999

RSP value to be used when RSP input is
at minimum.

Range min

OpnA =
rSPi