3 valve control tuning (pi with linear outputs) – Despatch P1400+ Temperature Controller User Manual
Page 60

54
9.2 Dual Control Tuning (PID with Primary and Secondary Outputs)
This simple tuning technique balances the need to reach setpoint quickly, with the wish to limit
setpoint
overshoot at start-up and during process changes. It determines values for the
Primary
Proportional Band
(
Pb_P
),
Secondary Proportional Band (
Pb_S
)
,
Integral Time Constant
(
ArSt
)
and
Derivative Time Constant
(
RAte
) that allow the
PID control
algorithm to give acceptable
results in most applications that use
dual control
(e.g. Heat & Cool).
CAUTION:
This technique is suitable only for processes that are not harmed by large fluctuations
in the process variable.
1. Tune the controller using only the Primary Control output as described in the
Single Control
Tuning
section above.
2. Set
Pb_S
to the same value as
Pb_P
and monitor the operation of the controller in dual
control mode. If there is a tendency to oscillate as the control passes into the Secondary
Proportional Band, increase the value of
Pb_S
. If the process appears to be over-damped
in the region of the Secondary Proportional Band, decrease the value of
Pb_S
.
3. When the PID tuning values have been determined, if there is a kick to the process
variable as control passes from one output to the other, set the Overlap/Deadband
parameter to a positive value to introduce some overlap. Adjust this value by trial and
error until satisfactory results are obtained.
9.3 Valve Control Tuning (PI with Linear Outputs)
This tuning technique is used when controlling a
modulating valve
requiring a linear (mA/VDC)
signal for its positioning circuitry. It determines values for the
Primary Proportional Band
(
Pb_P
),
and
Integral Time Constant
(
ArSt
). The
Derivative Time Constant
(
RAte
) is normally set to zero
(OFF). This
PI Control
minimises valve wear while giving optimal process control.
CAUTION:
This technique is suitable only for processes that are not harmed by large fluctuations
in the process variable.
1. Set the setpoint to the normal operating process value (or to a lower value if overshoot
beyond this value is likely to cause damage).
2. Set the
Primary Proportional Band
to the minimum value (i.e. set
Pb_P
= 0.5%).
3. Set the
Integral Time Constant
to the maximum value (i.e. set
ArSt
= 99.59).
4.
Set the
Derivative Time Constant
to OFF (i.e. set
RAte
= 0.00).
5.
Using manual control ensure that the valve is positioned away from its end stops.