beautypg.com

Despatch P1400+ Temperature Controller User Manual

Page 92

background image

86

Display value =

rSPo

, default value = 0.

Also refer to

Remote Setpoint

,

Scale Range Upper Limit

and

Scale Range Lower Limit

.

Retransmit Output

Type: General Definition

A linear DC voltage or mA output signal, proportional to the Process Variable or Setpoint, for use by
slave controllers or external devices, such as a Data Recorder or PLC. The output can be scaled to
transmit any portion of the input or setpoint span.
Also refer to

Input Span

,

Master & Slave

,

Process Variable

and

Setpoint

.

Retransmit Output 1 Scale Maximum

Type: General Parameter

Scales a linear output module in slot 1 that has been set up to retransmit PV or SP. Retransmit
Scale Maximum defines the value of the process variable, or setpoint, at which the output will be at
its maximum value. E.g. for a 0 to 5V output, the value corresponds to 5V. It may be adjusted within
the range -1999 to 9999; the decimal position is always the same as that for the process variable
input. If this parameter is set to a value less than that for Retransmit Output 1 Scale Minimum, the
relationship between the process variable/setpoint value and the retransmission output is reversed.
Display code =

ro1H

, default value = Scale Range Upper Limit.

Also refer to

Process Variable

,

Retransmit Output

,

Retransmit Output 1 Scale Minimum

,

Scale

Range Upper Limit

and

Setpoint

.

Retransmit Output 1 Scale Minimum

Type: General Parameter

Scales a linear output module in slot 1 that has been set up to retransmit PV or SP. Retransmit
Scale Minimum defines the value of the process variable, or setpoint, at which the output will be at
its minimum value. E.g. for a 0 to 5V output, the value corresponds to 0V. It may be adjusted within
the range -1999 to 9999; the decimal position is always the same as that for the process variable
input. If this parameter is set to a value greater than that for Retransmit Output Scale Maximum, the
relationship between the process variable/setpoint value and the retransmission output is reversed.
Display code =

ro1L

, default value = Scale Range Lower Limit.

Also refer to

Process Variable

,

Retransmit Output

,

Retransmit Output 1 Scale Maximum

,

Scale

Range Lower Limit

and

Setpoint

.

Retransmit Output 2 Scale Maximum

Type: General Parameter

Defines the value of the process variable, or setpoint, at which Retransmit Output 2 will be at its
maximum value. It is similar to Retransmit Output 1 Scale Maximum.
Display code =

ro2H

, default value = Scale Range Upper Limit.

Also refer to

Process Variable

,

Retransmit Output

,

Retransmit Output 2 Scale Minimum

,

Scale

Range Upper Limit

and

Setpoint

.

Retransmit Output 2 Scale Minimum

Type: General Parameter

Defines the value of the process variable, or setpoint, at which Retransmit Output 2 will be at its
minimum value. It is similar to Retransmit Output 1 Scale Minimum.
Display code =

ro2L

, default value = Scale Range Lower Limit.

Also refer to

Process Variable

,

Retransmit Output

,

Retransmit Output 2 Scale Maximum

,

Scale

Range Lower Limit

and

Setpoint

.

Retransmit Output 3 Scale Maximum

Type: General Parameter

Defines the value of the process variable, or setpoint, at which Retransmit Output 3 will be at its
maximum value. It is similar to Retransmit Output 1 Scale Maximum.
Display code =

ro3H

, default value = Scale Range Upper Limit.