Parameter

Lower
Display

Upper
Display

Description

Default

Value

When
Visible

Remote
Setpoint Offset

rSPo

Offset applied to RSP value. Constrained
within Scale Range Upper Limit and
Scale Range Lower Limit.

0

OpnA =
rSPi

Configura-

tion Mode Lock
Code

CLoc

0000

to

9999

9999

9999

9999

20

Always

*Note:
Alarm parameters marked * are repeated in Setup Mode.

**Note:

If

diGi

or

diG2 = diS1

the remote setpoint input feature is disabled. The instrument uses the

two internal setpoints (SP1 & SP2) instead.
If

diGi

and

diG2

are set to the same value, the status of digital input 2 will take precedence

over digital input 1.

8.2 1400+ – Setup Mode

This mode is normally selected only after

Configuration Mode

has been completed, and is used

when a change to the process set up is required. It can affect the range of adjustments available in

Operator Mode

. Using the PC Configurator software, it is possible to configure an Extended

Operator Mode. Setup Mode parameters are moved into Operator Mode, and these parameters
appear after the normal Operator Mode screen sequence has been completed.

Note:
Entry into Setup Mode is security-protected by the Setup Mode lock code.

Entry into the Setup Mode

Hold down and press to enter the Select Mode

Press or to navigate to the Setup Mode option, then press to enter Setup
Mode.

Scrolling through Parameters & Values

Press to scroll through the parameters (refer to the table below) and their values.

Changing Parameter Values

Press to select the required parameter, then press or to set the value as
required.

Once the displayed value is changed the effect is immediate. No confirmation of the change
is required.

Note:
If there is no key activity for two minutes the instrument returns to the operator mode.