Despatch P1400+ Temperature Controller User Manual

Page 39

background image

33

Changing Parameter Values

Press to navigate to the required parameter, then press or to set the value as
required.

Once the value is changed, the display will flash to indicate that confirmation of the change is
required. The value will revert back if not confirmed within 10 seconds.

Press to accept the change.

Or

Press to reject the change and to move onto the next parameter.

Hold down and press to return to Select Mode.


Note:
If there is no key activity for 2 minutes the instrument returns to the operator mode.

Table 10.

1400+ Configuration Mode Parameters

Parameter

Lower
Display

Upper
Display

Description

Default

Value

When
Visible

bC

B type: 100 to 1824 ºC

bF

B type: 211 to 3315 ºF

CC

C type: 0 to 2320 ºC

CF

C type: 32 to 4208 ºF

JC

J type: -200 to 1200 ºC

JF

J type: -328 to 2192 ºF

J

.

C

J type: -128.8 to 537.7 ºC
with decimal point

J

.

F

J type: -199.9 to 999.9 ºF
with decimal point

K

C

K type: -240 to 1373 ºC

K

F

K type: -400 to 2503 ºF

k

.

C

K type: -128.8 to 537.7 ºC
with decimal point

K

.

F

K type: -199.9 to 999.9 ºF
with decimal point

LC

L type: 0 to 762 ºC

LF

L type: 32 to 1403 ºF

Input type and
Range

InPt

L

.

C

L type: 0.0 to 537.7 ºC
with decimal point

JC

for Europe

JF

for USA

Always