Despatch P1400+ Temperature Controller User Manual
Page 46
40
Table 11.
1400+ Set Up Mode Parameters
Parameter
Lower
Display
Upper Display
Adjustment Range
Default
Value
When
Visible
Input Filter Time
constant
FiLt
OFF, 0.5 to 100.0 secs in
0.5 sec increments
2222
.
0000
Always
Process Variable Offset
OFFS
±
Span of controller
0000
Always
Primary Power
PPW
The current Primary
Output Power. Read Only.
N/A
Always
Secondary Power
SPW
The current Secondary
Output power. Read Only.
N/A
Ctyp
=
duAL
Primary Output
Proportional Band
Pb_P
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
10
10
10
10
.
0000
Always
Secondary Output
Proportional Band
Pb_S
0.0% (ON/OFF control)
and 0.5% to 999.9% of
input span.
10
10
10
10
.
0000
Ctyp
=
duAL
Automatic Reset
(Integral Time
Constant)
Arst
0.01 to 99.59 (1 sec to 99
mins 59 secs) and OFF
5555
.
00
00
00
00
Pb_P
is not
0000
.
0000
Rate (Derivative Time
Constant)
rATE
0.00 to 99.59 (OFF to 99
mins 59 secs)
1111
.
15
15
15
15
Pb_P
is not
0000
.
0000
Overlap/Deadband
OL
-20% to +20% of the sum
of the Primary and
Secondary Proportional
Bands
0000
Pb_P
is not
0000
.
0000
Manual Reset (Bias)
biAS
0% to 100% (-100% to
100% if
Ctyp
=
duAL
)
25
25
25
25
Pb_P
is not
0000
.
0000
Primary Output
ON/OFF Differential
diFP
0.1% to 10.0% of input
span (enter in % span)
0000
.
5555
Pb_P
=
0000
.
0000
Secondary Output
ON/OFF Differential
diFS
0.1% to 10.0% of input
span (enter in % span)
0000
.
5555
Pb_S
=
0000
.
0000
Primary and Secondary
Output ON/OFF
Differential
diFF
0.1% to 10.0% of input
span (enter in % span)
0000
.
5555
Pb_P
and
Pb_S
=
0000
.
0000
Setpoint Upper Limit
SPuL
Current Setpoint value to
Scale Range Maximum
Range
Max.
Always
Setpoint Lower limit
SPLL
Scale Range Minimum to
current Setpoint value
Range Min Always
Primary (Heat) Output
Upper Power Limit
OPuL
0% to 100% of full power
100
100
100
100
Pb_P
is not
0000
.
0000
Output 1
Cycle Time
CT1
0.5, 1, 2, 4, 8, 16, 32, 64,
128, 256 or 512 secs.
Not applicable to linear
outputs
32
32
32
32
USE1
= Pri
or
Sec
or
bus