beautypg.com

Despatch P1400+ Temperature Controller User Manual

Page 61

background image

55

6. Follow the instructions in the diagram below. At each stage, allow sufficient settling time

before moving on to the next stage.

Table 15.

Manually Tuning Valve Control

Time

P

ro

c

e

s

s

V

a

ri

a

b

le

T

b

Time

P

ro

c

e

s

s

V

a

ri

a

b

le

T

a

START

Apply Power to

the load.

Does the

PV

continuously

Oscillate?

Note the time

interval T

a

Set

Pb_P

= 0.8%

Set

ArSt

= T

a

Are the

Oscillations

decaying to

zero?

Multiply

Pb_P

setting by 1.5

END

Note the period

of the decaying

oscillations (T

b

)

Multiply

Pb_P

setting by 1.5

Set

ArSt

= T

b

/2


No

Yes

Yes

No

The controller is now tuned.

Fine-tuning may be required

to optimise the controllers

response