beautypg.com

Despatch P1400+ Temperature Controller User Manual

Page 96

background image

90

setpoint at power up, or when switching back to automatic mode from manual control, will be equal
to the current process variable value. The actual setpoint will rise/fall at the ramp rate set, until it
reaches the target setpoint value. Setpoint ramping is used to protect the process from sudden
changes in the setpoint, which would result in a rapid rise in the process variable.
Display code =

rP

, default setting = OFF (blank).

Also refer to

Manual Mode

,

Setpoint

,

Setpoint Ramp Enable

and

Setpoint Select

.

Setpoint Select

Type: Controller Parameter

This Operator Mode parameter is available if the remote setpoint feature is in use and setpoint
select is enabled, Setpoint Select defines whether the local or the remote setpoint will be the Active
Setpoint. It can be set to

diGi

,

LSP

, or

rSP

. If a digital input has been configured for local/remote

setpoint selection, the default setting is

diGi

. This means the status of the digital input will determine

which setpoint is active. Otherwise the user can only choose

LSP

, or

rSP

. The active setpoint is

indicated by prefixing its legend with the “_ “ character. E.g. the local setpoint legend is _

____

LSP

,

when it is active and

LSP

when it is inactive.

If a digital input has been configured to select local/remote SP, setting Setpoint Select to

LSP

, or

rSP

will override the digital input and the active SP indication changes to *.

Display code =

SPS

.

Also refer to

Active Setpoint

,

Remote Setpoint

,

Setpoint

and

Setpoint Select Enable

.

Setpoint Select Enable

Type: Controller Parameter

If the remote setpoint feature is in use, this determines whether operator selection of setpoints is
enabled or disabled. If enabled, the Setpoint Select parameter is available in operator mode. If
Setpoint Select is disabled again, the active setpoint will remain at its current status.
Display code =

SSEn

, default setting =

diSA

(disabled).

Also refer to

Remote Setpoint

and

Setpoint

.

Solid State Relay (SSR)

Type: General Definition

An external device manufactured using two Silicone Controlled Rectifiers, which can be used to
replace mechanical relays in most AC power applications. As a solid state device, an SSR does not
suffer from contact degradation when switching electrical current. Much faster switching cycle times
are also possible, leading to superior control. The instrument’s SSR Driver output is a time
proportioned 10VDC pulse, which causes conduction of current to the load when the pulse is on.
Also refer to

Cycle

Time,

Time Proportioning Control

,

and Triac

.

Solenoid Valve

Type: General Definition

An electromechanical device to control gas or liquid flow. It has just two states, open or closed. A
spring holds the valve closed until a current is passed through the solenoid coil forces it open.
Standard Process Controllers with Time Proportioned outputs are used to control solenoid valves.
Solenoid valves are often used with high/low flame gas burners. A bypass supplies some gas at all
times, but not enough to heat the process more than a nominal amount (low flame). A controller
output opens the solenoid valve when the process requires additional heat (high flame)..
Also refer to

Modulating Valves

and

Time Proportioning Control

.

Tare

Type: Indicator Parameter

When an Indicator’s Tare function has been enabled, the operator can set the current Process
Variable input value to be displayed as zero. This function may be used to easily eliminate any offset
on the input signal, e.g. when a transducer output is not giving a true zero value. It may also be used
in applications displaying the weight of a product, to remove the weight of a container before
starting. When Tare is activated, the instrument automatically sets the PV Offset to an equal, but
opposite value to the current measured value.