Upgrading the nxa-rgb and nxa-avb/rgb firmware – AMX Modero NXD/NXT-1200VG User Manual
Page 133
Upgrading Modero Firmware
119
VG-Series Modero Touch Panels
Upgrading the NXA-RGB and NXA-AVB/RGB Firmware
1.
Identify the Device number of the target panel being used for firmware routing to the accessories.
2.
Complete the instructions for configuring the NetLinx Master for IP communication found in the Step 1:
Prepare the Master for communication via an IP section on page 113.
3.
Press the grey Front Setup Access button for 3 seconds to open the Setup page.
4.
Press the Video Adjustment > RGB Adjustment buttons to open the RGB Adjustment page (FIG. 101).
This page displays the firmware for both the internal NXA-RGB card and the communicating external
NXA-AVB/RGB Breakout Box (BOB).
5.
Follow the procedures outlined within the Step 2: Upgrade the NXA-BASE/B firmware via an IP section
on page 117.
If the Base Version field displays 0.00, this means there was an error in the firmware
download process. Re-install the base firmware and re-confirm that the new base
version no longer reads 0.00.
FIG. 101
RGB Adjustment page (showing the default values)
Incoming signal shown in the background
Firmware version of the NXA-RGB card
Firmware version of the NXA-AVB/RGB
If firmware is updated to either the panel or the breakout box, both units must be
power-cycled for the panel to detect and display the new BOB firmware version.