5. Commissioning
5−83
Festo GDCP−SFC−LACI−DN−EN en 0812NH
Parameter / Description
CI
FCT
PNU
Out2: Setting condition rising/falling
Value = 0: The output is set if the reference value accrued from lower
values has been reached in accordance with 2422/04h.
Value = 1: The output is set if the reference value accrued from higher
values has been reached in accordance with 2422/04h.
1255
x
2422/06h
Out2: Resetting condition rising/falling
Value = 0: The output is reset if the reference value accrued from lower
values has been reached in accordance with 2422/05h.
Value = 1: The output is reset if the reference value accrued from higher
values has been reached in accordance with 2422/05h.
1256
x
2422/07h
Out2: Delay
Delay time in [ms] after a resetting condition has occurred. The output is
not reset until the delay time has expired (= switch−off delay).
1257
x
2422/08h
Out2: Inverted
0 = not inverted
1 = inverted
This setting is not taken into account when the output is used for a
brake/clamping unit (see 2422/01h).
1258
x
2422/09h
Out2: PWM value
Duty cycle during a period of time. See Fig. 5/9.
Values: 1 ... 100 %
Value = 0 deactivates the pulse−width modulation
1259
x
2422/0Ah
Tab. 5/21:
Parameters for the local digital outputs