Section 9. Programming

TrigVar-Controls whether or not data records are written to storage. Data

records are written to storage if TrigVar is true and if other conditions, such

as DataInterval (), are met. Default setting is -1 (True). TrigVar may be a

variable, expression, or constant. TrigVar does not control intermediate

processing. Intermediate processing is controlled by the disable variable,

DisableVar, which is a parameter in all output processing instructions (see

Output Processing Instructions

(p. 81)).

Read More!

TrigVar and DisableVar - Controlling Data Output and Output

Processing

(p. 125) discusses the use of TrigVar and DisableVar in special

applications.

Size-Table size is the number of records to store in a table before new data

begins overwriting old data. If "10" is entered, 10 records are stored in the

table -- the eleventh record will overwrite the first record. If "-1" is entered,

memory for the table is automatically allocated at the time the program

compiles. Auto allocation is preferred in most applications since the

CR200(X) sizes all tables such that they fill (and begin overwriting the

oldest data) at about the same time. Approximately 2K bytes of extra data

table space is allocated to minimize the possibility of new data over writing

the oldest data in ring memory when support software collects the oldest

data at the same time new data are written. These extra records are not

reported in the Status Table and are not reported to the support software and

so are not collected.

CRBASIC EXAMPLE. Definition and Use of a Data Table

(p. 79) creates a data

table named "OneMin", stores data once a minute as defined by DataInterval (),

and retains the most recent records in SRAM, up to the automatically allocated

memory limit. DataRecordSize entries in the status table report allocated

memory in terms of number of records the tables hold.

9.7.1.2 DataInterval () Instruction

DataInterval () instructs the CR200(X) to write data records at the specified

interval. The interval is independent of the Scan () / NextScan interval;

however, it must be a multiple of the Scan () / NextScan interval. The data

interval must be at least one minute.

DataInterval does not override the trigger condition in the DataTable instruction.

If the trigger is not set always true by entering a constant, it is a condition that

must be met in addition to the time interval before data will be stored.

9.7.1.3 Output Processing Instructions

Data storage processing ("output processing") instructions determine what data

are stored in the data table. When a data table is called in the CRBASIC

program, data storage processing instructions process variables holding current

inputs or calculations. If trigger conditions are true, e.g. the required interval has

expired, processed values are stored ("output") in the data table. In

CRBASIC

EXAMPLE. Definition and Use of a Data Table

(p. 79), three averages are

stored.

81