Section 4. Sensor Support

When a pulse channel is configured for pulse input mode, an internal 100 kΩ

pull-up resistor to +5 Volt on the P_SW input is automatically employed. This

pull-up resistor accommodates open-collector (open-drain) output devices for

high-frequency input. An external 100 kΩ pull-up resistor connecting Battery+

to P_LL, C1, or C2 must be added to perform pulse counting on any of those

channels (See

Multiple Switch Closure Measurements

p. 112).

The maximum input voltage on P_SW is 4 volts. For C1 and C2 the maximum

input voltage is 6.5 volts.

4.4.1.2 Low-Level AC (P_LL)

Rotating magnetic pickup sensors commonly generate AC output voltages

ranging from millivolts at low rotational speeds to several volts at high

rotational speeds. Channel P_LL contains internal signal conditioning hardware

for measuring low-level AC output sensors. P_LL measure signals ranging

from 20 mV RMS (±28 mV peak) to 14 V RMS (±20 V peak). Internal AC

coupling is incorporated in the low-level AC hardware to eliminate DC offset

voltages of up to ±0.5 V.

4.4.2 Pulse Input on Digital I/O Channels C1–C2

Read More! Review digital I/O channel specifications in

Specifications

p. 35.

Review pulse counter programming in CRBASIC Help for the PulseCount ()

instruction.

Digital I/O channels C1 – C2 can be configured to measure pulse input signals.

Pulse input signals require external 100 kΩ pull-up resistors to be connected

between Battery+ and the control ports. Maximum input voltage level is 6.5 V.

If pulse inputs greater than +6.5 V need to be measured, external signal

conditioning must employed. Contact Campbell Scientific for further

information.

Low-level AC signals cannot be measured directly on channels C1 – C2.

4.5 Period Averaging Measurements

The CR200(X) can measure the period of a signal on any single-ended analog

input channel (SE 1 - 5). The specified number of cycles are timed with a

resolution of 70 ns, making the resolution of the period measurement 70 ns

divided by the number of cycles chosen.

Cycles are counted as the input voltage transitions from less than 0.9 volts to

more than 2.1 volts. The maximum input voltage must be less than 4 volts. The

maximum frequency that can be detected is 150 kHz.