Section 3. Overview

Advantages of PakBus:

Simultaneous communication between the CR200(X) and other devices.

Peer-to-peer communication-no PC required.

Other PakBus dataloggers can be used as "sensors" to consolidate all data

into one CR200(X).

Routing - the CR200(X) cannot act as a router, passing on messages

intended for another logger, but other dataloggers can. PakBus supports

automatic route detection and selection.

Datalogger to datalogger communications-special CRBASIC instructions

simplify transferring data between dataloggers for distributed decision

making or control.

In a PakBus network, each datalogger is set to a unique address before

being installed in the network. Default PakBus address is 1. To

communicate with the CR200(X), the datalogger support software (see

Telecommunications and Data Retrieval

(p. 131)) must know the

CR200(X)'s PakBus address. The PakBus address is changed using the

DevConfig software, CR200(X) status table, or PakBus Graph software.

3.1.7.2 Modbus

Read More! See

Modbus

(p. 139).

The CR200(X) supports Modbus Master and Modbus Slave communication for

inclusion in Modbus SCADA networks.

3.1.8 Maintenance Overview

Read More! See Care and Maintenance.

With reasonable care, the CR200(X) should give many years of reliable service.

3.1.8.1 Protection from Water

The CR200(X) and most of its peripherals must be protected from moisture.

Moisture in the electronics will seriously damage, and probably render un-

repairable, the CR200(X). Water can come from flooding or sprinkler irrigation,

but most often comes as condensation. In most cases, protecting from water is as

easy as placing the CR200(X) in a weather tight enclosure with desiccant and

elevating the enclosure above the ground. The CR200(X) is shipped with

desiccant to reduce humidity. Desiccant should be changed periodically. Do not

completely seal the enclosure if lead acid batteries are present; hydrogen gas

generated by the batteries may build up to an explosive concentration.

32