Section 3. Overview

3.1.3.2 Voltage Outputs

Read More! See

Control Output

(p. 49).

Switched Analog Output (Excitation): two channels (VX1/VX2) for

precise voltage excitation ranging from +2500 mV or +5000 mV. These

channels are regularly used with resistive bridge measurements. Each

channel will source up to 25 mA.

Digital I/O: 2 channels (C1 - C2) configurable for on / off and pulse output

duration.

Switched 12 Volts (SW Battery): (switch on / off ) primary voltage under

program control for control of external devices requiring 12V DC, such as

humidity sensors. SW Battery can source up to 900 mA. See

TABLE.

Current Sourcing Limits

p. 38.

CR200(X) used as a PLC (programmable logic controller): Utilizing

peripheral relays and analog output devices, the CR200(X) can manage

binary and variable control devices through the following output channels:

Digital I/O: 2 channels (C1/C2) configurable for pulse output duration.

Switched 12 Volts (SW Battery): (switches on/off) primary voltage

under program control for control of external devices requiring 12V

DC, such as humidity sensors. SW Battery can source up to 900 mA.

See

TABLE. Current Sourcing Limits

p. 38.

3.1.3.3 Grounding Terminals

Read More! See

Grounding

(p. 55).

Proper grounding will lend stability and protection to a data acquisition system.

It is the easiest and least expensive insurance against data loss-and the most

neglected. The following terminals are provided for connection of sensor and

datalogger grounding:

Signal Grounds: 6 ground terminals ( ) used as reference for single-ended

analog inputs, pulse inputs, excitation returns, and as a ground for sensor

shield wires. Signal returns for pulse inputs should use terminals located

next to pulse inputs.

Power Grounds: 6 terminals (G) used as returns for 5V, SW Battery, 12V,

and C1-C2 outputs. Use of G grounds for these outputs minimizes

potentially large current flow through the analog voltage measurement

section of the wiring panel, which can cause single-ended voltage

measurement errors.

Ground Lug: 1 terminal ( ), the large ground lug is used to connect a

heavy gage wire to earth ground. A good earth connection is necessary to

secure the ground potential of the datalogger and shunt transients away

from electronics. Minimum 14 AWG wire is recommended.